Warranty | Unless otherwise specifically indicated and exempted in the product description, there is 1 year parts and/or replacement only manufacturer’s limited warranty from the date of purchase on all products contained on this website. Ductless mini split air conditioning systems purchased before May 31, 2018 have an additional 4 years replacement only limited warranty coverage for the compressor (5 years total compressor coverage). Ductless mini split air conditioning systems purchased after May 31, 2018 include a 5 year parts replacement only manufacturer's limited warranty for the entire system from date of purchase, with an additional 2 years coverage for the compressor only (7 years total compressor coverage). Labor is not included in this warranty and is hereby expressly excluded. Any defective product or components thereof may be repaired or replaced at our/manufacturer’s option. The buyer shall be responsible for the process and cost of returning the faulty product or part to us for repair and/or replacement. We will however return the repaired or replaced items or parts to the buyer at our expense within the warranty period via standard ground shipment methods. We shall not be responsible for faulty installation, operation or maintenance of the product and as such we recommend installation and assembly, where applicable, only by certified and qualified professionals. It is the responsibility of each purchaser to determine whether the particular product is compliant with and permissible for use pursuant to the applicable rules, codes and/or regulations, if any, and suitable for particular and/or intended use and/or operation therein. We make no representations or warranties whatsoever concerning the suitability of any merchandise for a particular use or purpose. Damage resulting from failure to use, install or maintain the product in a manner consistent with our/manufacturer’s recommendations shall render the warranty void. AC-World, at its option, may request a report from a qualified technician prior to honoring a warranty claim. All warranties specifically excludes any consequential and/or incidental damages. A Return Merchandise Authorization (RMA) Number must be obtained from AC-World prior to return of any equipment. Please email sales@ac-world.com to obtain a RMA (Return Merchandise Authorization) form. |
9000 BTU ~ 24000 BTU
|
RAMSOND, CELIERA, AMVENT OE Series SEER 16 |
|||
TIME | ON/OF | CODE | Description | HVAC Technician test |
1 Time | x | EH00 | Indoor Unit EEPROM Parameter error | Test indoor/outdoor board |
2 Times | x | EL 01 | Indoor/Outdoor Units Communication Voltage | Test indoor /outdoor voltage, Check cables communication, Inspect Boards |
3 Times | x | EH 02 | Zero-Crossing signal detection error(DC FAN ONLY) | Check Voltage ,Fan Motor |
4Times | x | EH03 | Indoor Fan Speed has been out of control | Check the fan Motor , Check voltage |
6Times | x | EH60 | Indoor room Temperature Sensor T1 open circuit or short | OHM Sensor, Check connection |
6 Times | x | EH61 | Evaporator Coil temperature sensor T2 open circuit or short | OHM Sensor ,Check connection |
8 Times | x | ELOC | Refrigerant leakage detection | Check for leaks and recharge the system |
9Times | x | EHOB | Communication Between indoor PCB and outdoor | Check voltage , Check cables |
1 Times | * | PC08 | Over Current protection | Check voltage |
5 Times | x | EC52 | Condenser coil temperature sensor T3 open or short | OHM Sensor, Check connection |
5 Times | x | EC54 | Compressor discharge temperature sensor open circuit or shorth | OHM sensor , Check connection |
5Times | x | EC51 | Outdoor EEPROM parameter error | Check Board |
12Times | x | EC07 | Outdoor fan speed has been out of control (dc fan only) | Check fan motor Ohm and voltage |
7Times | * | PC00 | IPM malfuction or IGBT over-strong current protection | Check board |
2Times | * | PC01 | DC voltage between P and N out of range | Check voltage, Inspect board |
3Times | * | PC02 | Hi temperature protection of compressor top or IPM heat sink | Check compressor, Check pressure |
5 Times | * | PC04 | Inverter compressor drive error | Check compressor, Check board |
FHOP | AP mode is active but there is no WFI kit installed | Only WIFI SYSTEM |
light information | X: OFF | O:ON | *: FLASHES IN 2 HZ |
DISCONTINUE SYSTEM |
||
REMOTE | MODEL | SERVICE MANUALS |
SEG,GWI,GWX,GW2,AX,GW3 | 2016 TO 2018 Service manuals | |
SEG,GWI,GWX,GW2,AX,GW3 | ||
GW2,GWX,GW3 | ||
KFR Series | ||
REMOTE | MODEL | SERVICE MANUALS |
KCD,KHP | Technician Service Manual | |
KCD,KHP |
CLICK ON THE LNK MANUFACTURER SERVICE MANUALS AND ERROR CODE |
OLMO WEBSITE SUPPORT LINK | Technical Support manuals |
COOPER & HUNTER SUPPORT LINK |